null Skip to main content

Dwyer Series 629C Wet/Wet Differential Pressure Transmitter w/ Remote Sensors, 100 PSI Range

SKU:
Please choose an option below
Manufacturer:
Dwyer
Product Type:
Pressure Transmitter
Size:
1/4 in. NPT
Weight:
4.75 LBS
$660.01 - $953.81
Adding to cart… The item has been added

The Series 629C Wet/Wet Differential Pressure Transmitter monitors differential pressure of air and compatible gases and liquids with 0.5% accuracy. The design employs dual pressure sensors converting pressure changes into a standard 4 to 20 mA output signal or field selectable voltage. Small internal volume and minimal moving parts result in exceptional response and reliability. The terminal block, as well as a zero adjustment button, are easily accessed under the top cover. The Series 629C, with the optional factory installed remote sensors, are connected to the unit, either via armored or shielded cable and available in 10 and 20' lengths. Installation is much simpler, reducing labor and material cost versus traditional copper piping installations and no need for valve manifolds. The 629C family has a robust NEMA 4X (IP66) construction, which is also available with an integral LCD for localized data monitoring. Applications: Flow elements, Heat exchangers, Filters, Coils, Chiller, Pumps.

Features

  • Powered by either DC or AC - take advantage of most readily available power source reducing installation costs
  • Optional LCD does not need a separate power supply - lowers installed cost
  • Selectable voltage range - provides flexible choice for changing design or inputs for process/HVAC controllers being used to monitor and control
  • Push button zero (versus trim pot) - more simple zeroing provides easy install and calibration reducing installation time and possibility of operator error.

Specifications

  • Service: Compatible gases and liquids
  • Wetted Materials: Without valve: 316, 316L SS.
  • Accuracy: ±0.5% FS (includes linearity, hysteresis & repeatability)
  • Stability: ±1% FS/year.
  • Temperature Limits: 0 to 200°F (-18 to 93°C).
  • Compensated Temperature Limits: 0 to 175°F (-18 to 79°C)
  • Thermal Effect: Avg 0.04%/°F (0.072%/°C) (includes zero and span).
  • Power Requirements: 2-wire: 10 to 35 VDC; 3-wire: 13 to 35 VDC or isolated 16 to 33 VAC (reverse polarity protected).
  • Output Signal: 2-wire: 4 to 20 mA; 3-wire: Field selectable 0 to 5, 1 to 5, 0 to 10, or 2 to 10 VDC
  • Zero and Units: Push buttons inside conduit enclosure.
  • Response Time: 400 msec.
  • Loop Resistance: Current output: 0 to 1250 Ω (max), Rmax = 50(Vps-10)
  • Voltage output: Minimum load resistance = 5 kΩ.
  • Current Consumption: 28 mA (max).
  • Electrical Connections: Removable terminal block; 1/2" female NPT conduit.
  • Process Connections: 1/4" female or male NPT.
  • Display: Optional 4-1/2 digit LCD field attachable display
  • Enclosure Rating: Designed to meet NEMA 4X (IP66).
  • Weight: 10.1 oz (286 g)

Downloads

Product Manual (PDF Download)

Product Manual (PDF Download)