The 9095DS valve is installed at the fill port of a storage tank. Designed for use in pressurized fill systems and requires a tight fill connection. The valve installs in a 2 inch female threaded opening of a low profile tank requiring a high level shut-off. The valve terminates the fill when the product reaches the Factory preset level.
The 9095SA comes with a 2" Part F for mounting directly to the valve or a 2" Part A when mounting the valve to a spill container or remote fill.Features
- Designed for fill applications that require a drop tube. (accepts a 1-1/2” male threaded drop tube)
- The valve design allows for full product flow until it reached the shut-off level
- The shut-off height is factory preset and is measured from the bottom of the attachment threads
- Typical flow rate is 26 GPM at 10 PSI pressure drop and 60 GPM at 60 PSI pressure drop
- 10 PSI & 5 GPM is the minimum flow requirement for the valve to operate
- Can be retrofitted to existing tanks
- Cushioned shut-off eliminates line shock
- Integral pressure relief feature allows for safe unloading at the completion of the fill operation
- Shut-off is activated by basic hydraulic principals
- Typical flow rates are 26 GPM at 10 PIS pressure drop and 60 GPM at 60 PSI pressure drop
Construction Details
- Adaptor: Anodized aluminum Part A or Part F
- Body: Anodized aluminum
- Float: Nitrophyl-N
- Plunger and dashpot: Brass
- Upper tube and float guard: Aluminum
- Linkage: Stainless steel
- Shut off mechanism: Anodized aluminum