Designed for installation on vertical tanks up to 9.5 meters in height, the 1619 mechanical vertical tank gauge provides a readout in meters and centimeters at ground level and includes a single level alarm relay output to activate an external alarm box (sold separately).
Note: Drop tube floats install through a 4 in. tank opening.
Features
- 9.5 m. line of sight viewing distance
- Easy to read from wide viewing angle
- Easy to install with single vertical pipe connection
- Easy to calibrate
- Installs through a 4 in. tank opening.
- Vapor is contained from the viewing area to prevent lens fogging
- Mounting options:
- Foot base
- Tank mount bracket for easy attachment to Uni-Strut Channel or other tank brackets
- Desired alarm level is set within gauge head
- The level alarm relay output wiring from the gauge has to be connected to the simple switch, dry contact input of an external alarm box (sold separately)
- Battery power module
- Located near alarm box
- Test button verifies alarm relay output circuit is operational
- One 3.6 volt lithium AA replaceable battery
- Anticipated battery life is 4 years
- Low battery light indicator
Specifications
- Body: Cast aluminum
- Gears and Gear Cogs: Acetal
- Hardware: Stainless steel (including captive screws on front cover)
- Float: Stainless steel standard float
- Cable: Stainless steel
- Pulleys: Cast aluminum
- Spring: 301 stainless steel
- Shaft Bushing: Stainless steel
- O-ring: FKM
- Lens Cover: Acrylic
- Power Module Enclosure: Polyester fiberglass
Downloads
1618 Mechanical Gauge - Installation and Maintenance Instructions (PDF Download)