Otis Instruments Omniguard Model 760 multi-spectrum infrared flame detector is designed to detect unwanted fires and output alarm information. The Model 760 senses infrared radiation in five discreet infrared wavelengths for early fire detection for maximum protection of people, machinery, and facilities. Utilizes the patented Omniguard Fire Event Algorithm for superior false alarm immunity and quick detection of hydrocarbon fueled fires. Otis Instrument flame detectors have an automatic self-test function to monitor the detector's ability to sense fires and report a fault condition when impaired. The self test feature also eliminates the need for any external test fixtures.
Notes: Swivel mount (20856) included. Other configurations available - Please call 1-800-333-3331 for more information.
Features
- Patented Fire Event Analysis (FEA) Algorithm for Superior False Alarm Immunity
- Operating Temperature: -40°F to 185°F (-40°C to 85°C)
- User-Selectable Sensitivities
- Long Range Detection
- Advanced Through-the-Lens Diagnostic Self-Test (No External Test Source Required)
- Self-Contained, Explosion-Proof Enclosure
- Field Configurable Relays and Sensitivity
- State-of-the-Art Microprocessor Control
- Wide Field of View of 90°
- High Intensity, Localized Indication of Proper Operation: Fire or Fault
- FM, CSA, IECEx and ATEX Approved
- 5-Year Warranty
Specifications
- Model: Omniguard 760
- Operating Temperature: -40°F to 185°F (-40°C to 85°C)
- Spectral Response: Infrared Peak Sensitivities of 2.2 μm, 3.7 μm, 4.4 μm, and 5.8 μm
- Nominal Voltage: 24 VDC (Ripple Voltage <240mV)
- Range: 20 to 30 VDC
- Power Consumption: 80 mA (Standby), 100 mA (Alarm), 160 mA (Auto and Manual Test)
- Output:
- Relay
- Relays (2): Fire, Trouble, Dry Contacts, Hermetically Sealed
- Rated: 2 A at 28 VDC (User Selects NO or NC)
- Fire Relay: Latching (Non-Latching Optional)
- Current Loop (Standard Version): 0 to 20 mA Output
- 20 mA = Fire
- 16 mA = Warning Fire IR
- 5 mA = Warning Ref IR
- 3 mA = Fire Relay Coil Fault
- 2 mA = Calibration Not Complete
- 1 mA = Self-Test Fault
- 0 mA = Current Loop Fault
- 4 mA = Normal
- Digital Output: RS-485 Modbus Serial I/O
- Product Dimensions: 4.5 in. H x 5.5 in. W x 4.9 in. D
- Total Weight: 5 lbs.
- Conduit Entry: 3/4-14 NPTF (M20-1.5 Optional)
- Optional Accessories:
- Portable Test Unit - Model 545
- Rain Shield - No. 23546
- Pole Mount for Swivel Mount - No. 26803
- Certifications & Approvals
- Class I, Division 1, Groups B, C & D (Explosion Proof)
- Class II, Division 1, Groups E, F & G (Dust Ignition Proof)
- TYPE 4X Weatherproof, Dust-Tight, Watertight
- CE0081 Ex d II 2 G/D
- Ex d IIB+H2 T5 Gb for Gas
- EX tb IIIC T100°C Db IP66 for Dust
- Copper-Free Aluminum Housing Coated to MIL-C-5541C, Class 3 (White)
Downloads
Omniguard Model 760 Data Sheet (PDF Download)
Omniguard Swivel Mount Data Sheet (PDF Download)