Otis Instruments Omniguard Model 860 UV/IR flame detector is designed to detect unwanted fires and output alarm information. The Model 860 senses ultraviolet radiation and infrared radiation in the appropriate wavelengths for early fire detection. Utilizes the patented Omniguard Fire Event Analysis Algorithm to provide superior false alarm immunity. Otis Instrument flame detectors have an automatic self-test function to monitor the detector's ability to sense fires and report a fault condition when impaired.
Notes: Swivel mount (20856) included. Other configurations available - Please call 1-800-333-3331 for more information.
Features
- Patented Fire Event Analysis (FEA) Algorithm for Superior False Alarm Immunity
- Operating Temperature: -40°F to 185°F (-40°C to 85°C)
- User-Selectable Sensitivities
- Long Range Detection
- Advanced Through-the-Lens Diagnostic Self-Test
- Self-Contained, Explosion-Proof Enclosure
- Field Configurable Relays and Sensitivity
- State-of-the-Art Microprocessor Control with Proprietary Fire Library
- Robust Weatherproof Enclosure for Indoor or Outdoor Applications
- Widest Field of View in the Industry of 120°
- High Intensity, Localized Indication of Fire or Fault
- Economical No-Test Version Available
- FM, CSA, IECEx and ATEX Approved
- All Inclusive 3-Year Warranty on Parts and Labor
Specifications
- Model: Omniguard 860
- Operating Temperature: -40°F to 185°F (-40°C to 85°C)
- Spectral Response:
- UV Peak Sensitivities of 0,22 μm
- Infrared Peak Sensitivities of 4.4 μm (Standard), and 2.9 μm and 4.4 μm (Dual Pass)
- Nominal Voltage: 24 VDC (Ripple Voltage <240mV)
- Range: 20 to 30 VDC
- Power Consumption: 90 mA (Standby), 110 mA (Alarm), 250 mA (Auto and Manual Test)
- Output:
- Relay
- Relays (2): Fire, Trouble, Dry Contacts, Hermetically Sealed
- Rated: 2 A at 28 VDC (User Selects NO or NC)
- Fire Relay: Latching (Non-Latching Optional)
- Current Loop (Standard Version): 0 to 20 mA Output
- 20 mA = Fire
- 16 mA = UV or IR Presence
- 4 mA = Ready
- 0 mA = 20
- Digital Output: Programmable RS-485 Modbus Serial Output
- Product Dimensions: 4.5 in. H x 5.5 in. W x 6 in. D
- Total Weight: 5 lbs. (Aluminum)
- Conduit Entry: 3/4-14 NPTF (M20-1.5 Optional)
- Optional Accessories:
- Portable Test Unit - Model 545 / 545
- Air Shield Assembly Kit - No. 8001023
- Rain Shield - No. 23546
- Pole Mount for Swivel Mount - No. 26803
- Certifications & Approvals
- Class I, Division 1, Groups B, C & D (Explosion Proof)
- Class II, Division 1, Groups E, F & G (Dust Ignition Proof)
- NEMA 4X Weatherproof, Dust-Tight, Watertight
- CE0081 Ex d II 2 G/D
- Ex d IIB+H2 T5 Gb for Gas on 660-0XXXX
- EX tb IIIC T100°C Db IP6X for Dust on 660-0XXXX
- Ex d IIB+H2 T4 Gb for Gas on 660-1XXXX
- EX tb IIIC T1 135°C Db IP6X for Dust on 660-1XXXX
- Copper-Free Aluminum Housing Conversion Coated to MIL-C-5541, Class 3 (White) - Standard
- Stainless Steel Housing with Passive Finish per MIL-5-5002C, Type 1 (Optional)
Downloads
Omniguard Model 860 Data Sheet (PDF Download)
Omniguard Swivel Mount Data Sheet (PDF Download)