null Skip to main content

Red Jacket® ISOTROL™ 1-8 Control Box, 120V

SKU:
Please choose an option below
Manufacturer:
Red Jacket
Weight:
3.00 LBS
$531.24 - $638.54
Adding to cart… The item has been added

The Red Jacket® ISOTROL™ 1-8 Control Box is the most versatile dispenser handle signal isolation system available. It provides a means to remove all external voltage sources, including feedback, during periods of maintenance and service of the dispensing equipment to meet NEC requirements.

The Red Jacket® ISOTROL™ 1-8 Control Box isolates handle signals between each dispenser and protects against wiring shorts and phasing issues. It is available with or without a built-in 30-amp 2HP rated relay.

  • ISOTROL™ 1-8 units without the relay are designed for use with the TLS-450PLUS or another component for motor control – IQ, standard control box or three phase magnetic starter and will accept up to eight individual dispenser signals.
  • ISOTROL™ 1-8R units with the relay bypass an ATG to activate one pump and will accept up to eight individual dispenser signals. They can also be utilized to activate a second pump in manifolded applications.

Note: Each configuration also has a 240VAC international equivalent. Please call 1-800-333-3331 for more information.

Features

  • Isolates the handle signals between each dispenser
  • Isolates and protects individual dispensers from wiring shorts or phasing issues
  • Isolates and protects technicians from dangerous feedback during service
  • Ready interface with the Red Jacket® IQ Control Box and/or the TLS-450PLUS
  • Compliant with NEC requirements for handle isolation
  • Accepts up to eight individual dispenser signals
  • If ordered without relay, it must be used with another component for motor control
  • Dedicated Automatic Tank Gauge (ATG) line leak output and coil for easy compatibility with Pressurized Line Leak Detection (PLLD)
  • Terminals are labeled for easy wiring and compatibility
  • May be used with all Red Jacket and competitive submersible turbine pumps
  • Easily retrofitted to existing locations

Specifications

  • Dimensions: Type 1 enclosure, 6 in. x 6 in. x 4 in.
  • DISP Inputs: 10 mA @120V or 240V 50/60 Hz
  • Control Circuit: 15 mA @ 120V 50/60 Hz or 240V 50/60 Hz
  • ATG Output: 750 mA @ 120V or 240V 50/60 Hz
  • Control Relay: 30A DPST 120/240VAC 50/60 Hz
  • Terminals:
    • 250V
    • 14-28 AWG
    • 10-18 AWG Main