Veeder Root's TLS4 Automatic Tank Gauge is a compact, powerful, and expandable console. Its combination of precision performance, customization, and ease of-use to deliver proven results make it ideal for small retail, commercial and industrial applications. The TLS4 has 12 universal sensor or probe inputs (when using only two-wire devices). These ATGs provide real-time access and automated alerts to critical site information anywhere in the world. The TLS4 tank level sensors eliminate manual dipping while providing a state-of-the-art interface with a web-based system, streamlining your wet stock management.

Note: Software included (0333434-001).

Features

  • Performance: The TLS4 Automatic Tank Gauge is a premier fuel inventory management solution - Delivers accurate, crucial information with streamlined inventory and compliance reporting
  • Protection: The TLS4 monitoring systems protects your fuel assets using sensors, probes and advanced software solutions to deliver accurate Underground Storage Tank (UST) and Aboveground Storage Tank (AST) information
  • Profitability: The compact and powerful monitoring system is extremely easy to use - View, configure, and control these ATGs using the graphical user interface or access remotely to manage multiple locations to improve efficiency and reliability
  • Web-Enabled: Take action to resolve on site issues remotely by connecting to settings and diagnostics on your automatic tank gauge using the web-enabled feature - View your site's status, run reports and make adjustments without being on site

Specifications

  • Type: TLS4 Automatic Tank Gauge, Color Touch Screen Display, EDIM, UL, Software Included
  • Part: 0860190-020
  • Operating Temperature: +32 to +122°F (0 to +50°C)
  • Storage Temperature: -40 to +158°F (-40 to +70°C)
  • Installation Location: NEMA 4 or indoors; must maintain Operating Temperature requirement stated above
  • Relative Humidity: 0-90% (non-condensing)
  • External Dimensions: 13 in. x 8 in. x 3.5 in. (33.02 cm. x 20.32 cm. x 8.89 cm.)
  • Construction: 16GA (0.060 in./0.1524 cm.) Powder Coated Steel
  • Console Power Wiring Requirements: AC Power Wiring - Wires carrying 120 or 240VAC from power panel to the console should be #14 AWG (or larger) wire for line, neutral & chassis ground (3); and 4 sq. mm, rated for at least 90C for barrier ground
  • Probe & Sensor to Console Wiring Requirements:
    • Wire Type - Shielded cable required regardless of conduit materiel or application - Shielded cable must be rated less than 100 picofarad per ft manufactured with a suitable material such as Carol C2534 or Belden 88760, 8760, or 8770. Cable must be oil and gas resistant
    • Wire Length - maximum 1,000ft (304.8m) to meet intrinsic safety requirements - Improper system operation could result for runs over 1,000ft (304.8m)
    • Wire Gauges - Color coded - shielded cable used in all installations. Wires should be #14 - #18 AWG stranded copper wire and installed as Class 2 circuits - As an alternate method when approved by the local authority having jurisdiction, #22 AWG wire such as 88761 may be suitable with the following requirements: wire run is less than 750ft (228.6m), Capacitance does not exceed 100 pF/foot, Inductance does not exceed 0.2 uH/ft.
  • System Power Requirements: Either AC input or DC input, but not both
    • Universal AC power supply: 100 to 249VAC, 50/60Hz, 2A max
    • DC power supply: +24VDC, 2A max. and +5VDC, 4A max. Um <= 250Vrms or 250VDC
  • Display Specifications: 7 in. (17.78 cm.) Color WVGA LCD touch screen display
  • Data Storage Features: SD Card
  • Software Security Features: Centralized Device Management provides support for network-wide upgrades and backups
  • Custom User Access: Front Panel Display control through user specific log-in; User defined roles to restrict access/functionality - Screen permissions can be limited to view, edit, perform
  • System Security:
    • Partitioned Ethernet Ports that can be used to separate user network from the internet
    • Port availability control: SSH Port (22), HTTPS Port (443), Serial Command Port (10001)
    • Reassign Port Numbers (i.e., HTTPS on 50443)
    • System Integrator CVE Scans & Fixes
    • Periodic System Updates to protect against persistent threats
  • Custom Alarm Features: Customizable for all alarms
  • Approvals: UL cUL, ATEX, IECEx, NEPSI, FCC, FMC, PESO