Appropriate for all hazardous areas where an intrinsically safe rating is required, including oil & gas and chemical installations.
Features
- Approved for intrinsically-safe applications in Class 1/Div. 1 hazardous areas
- Rugged stainless steel construction with ceramic sensor
- Available ranges include in/Hg up to 8,700 psi
- Wide range of mechanical and electrical connections
- ±0.5% FSO accuracy
- NEMA 4X and 6P / IP65, IP67 or IP68
- Approved for outdoor use
- Customizable
- 5 year warranty
Specifications
- Output Signal: 4-20 mA / Vs = 8-32 Vdc
- Accuracy: ± 0.5% FSO IEC 60770
- Permissible Load: Rmax = [(Vs - Vs min) / 0.02] Ohm
- Influence Effects:
- Supply: 0.05% FSO / 10 V
- Load: 0.05% FSO / kOhm
- Response Time: <10 ms
- Thermal Error:
- <±0.2% FSO / 10K
- In Compensated Range: -13°F to 185°F (-25°C to 85°C)
- Permissible Temperatures:
- Medium: -40°F to 257°F (-40°C to 125°C)
- Electronics Environment: -13°F to 185°F (-25°C to 85°C)
- Storage: -40°F to 212°F (-40°C to 100°C)
- Short Circuit Protection: Permanent
- Reverse Polarity Protection: No damage - No function
- Electromagnetic Protection: Emission and immunity according to EN 61326
- I.S. Protection: Class 1, Div. 1, Groups A, B, C & D
- Stability:
- Vibration: 10 g RMS (20 to 2,000 Hz)
- Shock: 500 g / 1 ms
- Polluiton Degree: 4, electrical equipment for outdoor use
- Housing: 316L Stainless Steel
- Pressure Port: 316 L Stainless Steel
- Wetted Parts:
- Seals: PN < 1450 psi: FKM70
- Diaphragm: Ceramic AI2O3 96%
- Weight: 140 g
- Current Consumption:
- Current: 25mA max
- Voltage: 7 mA max
- Operating Life: >100 x 10^6 Cycles
- Connecting Cables:
- Cable Capacitance: Signal line/shield and signal line/signal line: 160 pF/m
- Cable Inductance: Signal line/shield and signal line/signal line: 1 uH/m
Downloads
LIS Series Pressure Transmitter Technical Drawing (PDF Download)